4.8.2.1 Configuration of binary inputs and outputs via ACT
GUID-7102E264-F540-434C-96BA-47E72DA665B2 v1
LDCM hardware channels can be connected via ACT by right-clicking on the
chosen connection point, and then selecting Connect/Hardware Channel (see
Figure
46).
IEC10000241 V1 EN-US
Figure 46: Configuration of binary inputs and outputs via ACT
If an installed LDCM is not used, it should be removed or set to
binary mode without any connections, or the ChannelMode
parameter should be set to Blocked. Otherwise parallel LDCMs
may get blocked.
The following can be done in the Hardware Channel Allocation dialog:
Hardware Module selection
Hardware Channel selection
User Defined Name for the channel
IEC10000242-1-en.vsdx
IEC10000242 V1 EN-US
Figure 47: Hardware Channel Allocation dialog
1MRK 505 382-UEN B Section 4
Analog and binary signal transfer for line differential protection
Communication set-up 670/650 series 2.2 55
Application Guide