Function IEC 61850 IEC 60617 IEC-ANSI
Three-phase directional overcurrent
protection, low stage, instance 4
DPHLPDOC4 3I> -> (4) 67-1 (4)
Three-phase directional overcurrent
protection, high stage, instance 1
DPHHPDOC1 3I>> -> (1) 67-2 (1)
Three-phase directional overcurrent
protection, high stage, instance 2
DPHHPDOC2 3I>> -> (2) 67-2 (2)
Three-phase directional overcurrent
protection, high stage, instance 3
DPHHPDOC3 3I>> -> (3) 67-2 (3)
Three-phase directional overcurrent
protection, high stage, instance 4
DPHHPDOC4 3I>> -> (4) 67-2 (4)
Non-directional earth-fault protection,
low stage, instance 1
EFLPTOC1 Io> (1) 51N-1 (1)
FEFLPTOC1 FIo> (1) F51N-1 (1)
Non-directional earth-fault protection,
high stage, instance 1
EFHPTOC1 Io>> (1) 51N-2 (1)
Non-directional earth-fault protection,
instantaneous stage, instance 1
EFIPTOC1 Io>>> (1) 50N/51N (1)
Directional earth-fault protection, low
stage, instance 1
DEFLPDEF1 Io> -> (1) 67N-1 (1)
FDEFLPDEF1 FIo> -> (1) F67N-1 (1)
Directional earth-fault protection, low
stage, instance 2
DEFLPDEF2 Io> -> (2) 67N-1 (2)
FDEFLPDEF2 FIo> -> (2) F67N-1 (2)
Directional earth-fault protection, low
stage, instance 3
DEFLPDEF3 Io> -> (3) 67N-1 (3)
Directional earth-fault protection, low
stage, instance 4
DEFLPDEF4 Io> -> (4) 67N-1 (4)
Directional earth-fault protection, high
stage, instance 1
DEFHPDEF1 Io>> -> (1) 67N-2 (1)
Directional earth-fault protection, high
stage, instance 2
DEFHPDEF2 Io>> -> (2) 67N-2 (2)
Directional earth-fault protection, high
stage, instance 3
DEFHPDEF3 Io>> -> (3) 67N-2 (3)
Directional earth-fault protection, high
stage, instance 4
DEFHPDEF4 Io>> -> (4) 67N-2 (4)
Transient / intermittent earth-fault
protection, instance 1
INTRPTEF1 Io> -> IEF (1) 67NIEF (1)
Admittance-based earth-fault
protection, instance 1
EFPADM1 Yo> -> (1) 21YN (1)
Admittance-based earth-fault
protection, instance 2
EFPADM2 Yo> -> (2) 21YN (2)
Admittance-based earth-fault
protection, instance 3
EFPADM3 Yo> -> (3) 21YN (3)
Wattmetric-based earth-fault
protection, instance 1
WPWDE1 Po> -> (1) 32N (1)
Wattmetric-based earth-fault
protection, instance 2
WPWDE2 Po> -> (2) 32N (2)
Wattmetric-based earth-fault
protection, instance 3
WPWDE3 Po> -> (3) 32N (3)
Harmonics-based earth-fault
protection, instance 1
HAEFPTOC1 Io>HA (1) 51NHA (1)
Table continues on next page