EasyManua.ls Logo

ABB RET620 - Electromagnetic Compatibility Tests

ABB RET620
63 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 22. Electromagnetic compatibility tests
Description Type test value Reference
1 MHz/100 kHz burst disturbance test: IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002
Common mode 2.5 kV
Differential mode 2.5 kV
3 MHz, 10 MHz and 30 MHz burst disturbance
test:
IEC 61000-4-18
IEC 60255-22-1, class III
Common mode 2.5 kV
Electrostatic discharge test: IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001
Contact discharge 8 kV
Air discharge 15 kV
Radio frequency interference test:
10 V (rms)
f=150 kHz...80 MHz
IEC 61000-4-6
IEC 60255-22-6, class III
10 V/m (rms)
f=80...2700 MHz
IEC 61000-4-3
IEC 60255-22-3, class III
10 V/m
f=900 MHz
ENV 50204
IEC 60255-22-3, class III
20 V/m (rms)
f=80...1000 MHz
IEEE C37.90.2-2004
Fast transient disturbance test: IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
All ports 4 kV
Surge immunity test: IEC 61000-4-5
IEC 60255-22-5
Communication 1 kV, line-to-earth
Other ports 4 kV, line-to-earth
2 kV, line-to-line
Power frequency (50 Hz) magnetic field
immunity test:
IEC 61000-4-8
Continuous
1...3 s
300 A/m
1000 A/m
Pulse magnetic field immunity test: 1000 A/m
6.4/16 µs
IEC 61000-4-9
Damped oscillatory magnetic field immunity
test:
IEC 61000-4-10
2 s 100 A/m
1 MHz 400 transients/s
Voltage dips and short interruptions: 30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
Transformer Protection and Control 1MRS757846 A