ABB RET620 - Numerical Stabilized Low Impedance Restricted Earth-Fault Protection (LREFPNDF); Numerical Stabilized Low Impedance Restricted Earth-Fault Protection (LREFPNDF) Main Settings; High-Impedance Based Restricted Earth-Fault Protection (HREFPDIF); High-Impedance Based Restricted Earth-Fault Protection (HREFPDIF) Main Settings

ABB RET620
63 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 57. Numerical stabilized low impedance restricted earth-fault protection (LREFPNDF)
Characteristic Value
Operation accuracy Depending on the frequency of the current measured: f
n
±2 Hz
±2.5% of the set value or ±0.002 x I
n
Start time
1)2)
Minimum Typical Maximum
I
Fault
= 2.0 x set
Operate value
38 ms 40 ms 43 ms
Reset time < 40 ms
Reset ratio Typical 0.96
Retardation time < 35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n x f
n
, where n = 2, 3, 4, 5, …
1) Current before fault = 0.0, f
n
= 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Table 58. Numerical stabilized low impedance restricted earth-fault protection (LREFPNDF) main settings
Parameter Function Value (Range) Step
Operate value LREFPNDF 5...50 % 1
Restraint mode LREFPNDF None
2nd harmonic
-
Start value 2.H LREFPNDF 10...50 % 1
Minimum operate time LREFPNDF 40...300000 ms 1
Operation LREFPNDF Off
On
-
Table 59. High-impedance based restricted earth-fault protection (HREFPDIF)
Characteristic
Value
Operation accuracy At the frequency f = f
n
±1.5% of the set value or ±0.002 × I
n
Start time
1)2)
I
Fault
= 2.0 × set
Operate value
I
Fault
= 10.0 × set
Operate value
Typical 22 ms (±5 ms)
Typical 15 ms (±5 ms)
Reset time < 60 ms
Reset ratio Typical 0.96
Retardation time < 60 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Current before fault = 0.0 × I
n
, f
n
= 50 Hz
2) Includes the delay of the signal output contact
Table 60. High-impedance based restricted earth-fault protection (HREFPDIF) main settings
Parameter
Function Value (Range) Step
Operate value HREFPDIF 1.0...50.0 % 0.1
Minimum operate time HREFPDIF 40...300000 ms 1
Operation HREFPDIF Off
On
-
Transformer Protection and Control 1MRS757846 A
RET620
Product version: 2.0
38 ABB