EasyManua.ls Logo

ABB REX640 - Generator Application

ABB REX640
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CONDITION MONITORING
AND SUPERVISION
10100011001100
101100101110010
1100111011010
10110110110100
1010001100110010100011001100
101100101110010
1100111011010
10110110110100
OR
AND
PROTECTION AND CONTROL RELAY
Example of a combination of application packages for generator protection
PROTECTION
LOCAL HMI (OPTIONAL)
REX640
REMARKS
Total nr. of instances
ALSO AVAILABLE
- Disturbance and fault recorders
- Sequence event recorder
- Relay self-supervision
- User management and logging
- Logical and mathematical functions
- WebHMI
Ctrl
1)
Ind
2)
3I
3I
Io
3I
Io
EXC.
AVR
REK510
Uo
Io
3U
COMMUNICATION
Protocols:
IEC 61850-8-1/-9-2LE
Modbus
®
IEC 60870-5-103
DNP3
Interfaces:
Ethernet: TX (RJ45), FX (LC)
Serial: Serial glass fiber (ST),
RS-485
Redundant protocols:
HSR
PRP
Time synchronization:
SNTP
PTPv2
IRIG-B
Analog interface types
AIM1 + AIM2
+ RTD1
Current transformer 11
1)
Voltage transformer 9
1)
One of available current transformer
inputs is sensitive (0.2/1 A)
RTD measurement 10
mA input/output 2
3U
Uo
- 7-inch color touch screen
- Ready-made pages and
customizable pages
- Increased situational awareness
towards process
- Supports Relay testing and
commissioning
- Graphical editing of pages with
PCM600 tool
Master Trip
94/86
MEASUREMENT
- I, U, Io, Uo, P, Q, E, pf, f
- Sequence current/voltage measurement
- Limit value supervision
- RTD/mA measurement and mA output
APP8
CBCM
52CM
FUSEF
VCM, 60
MCS 3I
CCM
TCS
TCM
OPTS
OPTM
MCS 3I,I2
CCM 3I,I2
3Ihp>T
26/49HS
CONTROL AND INDICATION
Object
CB -
DC, 3 state
DC
8
6
ES 3
Control and status indication function for
primary object
Status indication function for primary
object
1)
2)
3
8
6
3
LOADPROF
LOADPROF
PQM3IH
PQM ITHD, IDC
PQM3VH
PQM VTHD, VDC
PQUUB
PQMV UB
PQMU
PQMV SWE,SAG,
INT
CVPSOF
SOFT
Io>>
67G/N-2
51G/N-2
3I>
67P/
51P-1
ARC
AFD
MAP
MAP
24×
I2/I1>
46PD
3Ith>F
49F
3U<
27
UFLS/R
81LSH
Io>>>
50G/50N
f>/f<,df/dt
81
12×
Uo>
59G/59N
U2>
59NS
U1>
59PS
U1<
27PS
3I>>>
50P
3I>/Io>BF
50BF
3I>
51P-1
3I>>
51P-2
3I(U)
51V
3I>>
67P/
51P-2
dIoHi>
87NHI
dIoLo>
87NLI
I2>
67Q
3U<R
27R
Io>
67G/N-1
51G/N-1
I2>M
46M
Io>>
51G/
51N-2
3I2f>
68HB
3I<
37
3U>
59
Io>
51G/
51N-1
APP7
APP11
APPLICATION PACKAGE FOR GENERATOR
AUTOSYNCHRONIZER
APPLICATION PACKAGE FOR POWER TRANSFORMER PROTECTION
APP8
APPLICATION PACKAGE FOR MACHINE PROTECTION
ADD-ON PACKAGE FOR SYNCHRONOUS MACHINE PROTECTION
APP7
ADD1
Is2t n<
49,66,48,50TDLR
P>/Q>
32R/32O
3dIHi>M
87HIM
3I<
37
Ist>
50TDJAM
I2>M
46M
n<
66
I2>>
46R
3Ith>M
49M
3dl>M/G
87M/87G
dHi_A>
87A
dHi_B>
87B
dHi_C>
87C
3Ith>T/G/C
49T/G/C
dUo>/Uo3H
64TN
U/f>
24
P<
32U
Z< G
21G
X<
40
OOS
78PS
Io>R
64R
PF<
55U
ESTART
EST,62
OI
79
25AU-
TOSYNC
SYNC
25
dHi_A>
87A
dHi_B>
87B
dHi_C>
87C
3Ith>T/G/C
49T/G/C
3dI>T
87T
U/f>
24
P>/Q>
32R/32O
P<
32U
Z< GT
21GT
AUTOSYNCG
25AUTOSYNCG
GUID-4DF9D45D-8F00-4294-AAD3-FDAE5CDC393B V2 EN
Figure 13. Generator application
F
igure 13 presents REX640 in a synchronous generator
application including a block transformer. The base
functionality is enhanced with the machine protection and
transformer protection application packages. The synchronous
machine add-on package supports the related protection
functions for a synchronous generator. Generator
autosynchronizer application packages support the
generator’s synchronized connection into the busbars, in both
1MRS759144 A
REX640
Product version: 1
16 ABB

Table of Contents

Related product manuals