ABB REX640 - High-Impedance Based Restricted Earth-Fault Protection (HREFPDIF)

ABB REX640
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 158. Numerical stabilized low-impedance restricted earth-fault protection (LREFPNDF) main settings
Parameter Function Value (Range) Step
Operate value LREFPNDF 5.0...50.0 %I
n
1
Minimum operate time LREFPNDF 40...300000 ms 1
Restraint mode LREFPNDF 1 = None
2 = Harmonic2
-
Start value 2.H LREFPNDF 10...50% 1
Operation LREFPNDF 1 = on
5 = off
-
Table 159. High-impedance based restricted earth-fault protection (HREFPDIF)
Characteristic
Value
Operation accuracy Depending on the frequency of the measured current: f
n
±2 Hz
±1.5% of the set value or ±0.002 × I
n
Start time
1)2)
Minimum Typical Maximum
I
Fault
= 2.0 × set
Operate value
I
Fault
= 10.0 × set
Operate value
16 ms
11 ms
21 ms
13 ms
23 ms
14 ms
Reset time Typically 40 ms
Reset ratio Typically 0.96
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Current before fault = 0.0, f
n
= 50 Hz, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Table 160. High-impedance based restricted earth-fault protection (HREFPDIF) main settings
Parameter
Function Value (Range) Step
Operate value HREFPDIF 1.0...50.0 %I
n
0.1
Minimum operate time HREFPDIF 40...300000 ms 1
Operation HREFPDIF 1 = on
5 = off
-
1MRS759144 A
REX640
Product version: 1
ABB 79