Table 28. Electromagnetic compatibility tests
Description Type test value Reference
1 MHz/100 kHz burst disturbance test IEC 61000-4-18
IEC 60255-26, class III
IEEE C37.90.1-2012
Common mode 2.5 kV
Differential mode 2.5 kV
3 MHz, 10 MHz and 30 MHz burst disturbance
test
IEC 61000-4-18
IEC 60255-26, class III
Common mode 2.5 kV
Electrostatic discharge test IEC 61000-4-2
IEC 60255-26
IEEE C37.90.3-2001
Contact discharge 8 kV
Air discharge 15 kV
Radio frequency interference test
10 V (rms)
f = 150 kHz...80 MHz
IEC 61000-4-6
IEC 60255-26, class III
10 V/m (rms)
f = 80...2700 MHz
IEC 61000-4-3
IEC 60255-26, class III
10 V/m
f = 900 MHz
ENV 50204
IEC 60255-26, class III
20 V/m (rms)
f = 80...1000 MHz
IEEE C37.90.2-2004
Fast transient disturbance test IEC 61000-4-4
IEC 60255-26
IEEE C37.90.1-2012
All ports 4 kV
Surge immunity test IEC 61000-4-5
IEC 60255-26
Communication 1 kV, line-to-earth
Other ports 4 kV, line-to-earth
2 kV, line-to-line
Power frequency (50 Hz) magnetic field
immunity test
IEC 61000-4-8
Continuous
1...3 s
300 A/m
1000 A/m
Pulse magnetic field immunity test 1000 A/m
6.4/16 µs
IEC 61000-4-9
Damped oscillatory magnetic field immunity test IEC 61000-4-10
2 s 100 A/m
1 MHz 400 transients/s
Voltage dips and short interruptions 30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
1MRS759144 A
REX640
Product version: 1
34 ABB

Table of Contents

Related product manuals