ABB | SACE Emax 2
Ekip Dip protection trip unit | 2 - Protections
39 | © 2017 ABB | 1SDH000999R0002 - ECN000058721 - Rev. B
I Protection
I
I3
t
t3
I
The I protection protects against instantaneous short circuit.
When the activation threshold is exceeded, the protection trips within a fixed non-adjustable time.
Parameters
The user can set the intervention threshold.
Parameter Description
Enable By setting the threshold dip-switches to the Off position, the protection is disabled.
Threshold I3
It defines the current value that if exceeded activates the protection (with reference
to the curve, it is the part parallel to the y-axis).
IMPORTANT: The I3 threshold set must be higher than the I2
threshold. An incorrect configuration returns an alarm signal.