ABB | SACE Emax 2
18 | © 2018 ABB | 1SDH001316R0002 - ECN000086018 - Rev. C Ekip Touch protection trip unit | 9 - G Touch protections
9 - G Touch protections
Availability (Performance)
The following is a complete list of the protections (and related parameters) available with all the Ekip G Touch and Ekip G Hi-Touch trip units, in
the Protections and Advanced menus:
Name Protection against
Th-
reshold
Time
Additional
parameters
(2)
Auxiliary functions
(2) (3)
S(V) Voltage control short-circuit X X X Trip enable, lock
RV
(1)
Residual voltage X X Trip enable, lock
RQ Reverse reactive power X X X Trip Enable, Lock
OQ Maximum reactive power X X Trip Enable, Lock
OP Maximum active power X X Trip Enable, Lock
UP
(4)
Minimum active power X X Trip Enable, Lock, Startup enable
(1)
Available for four-pole or three-pole circuit-breakers configured with external neutral voltage.
(2)
Detailed description in the Design Engineer's manual.
(3)
Locking Function available via Ekip Connect.
(4)
Not active for voltages <30V and if the circuit-breaker is open. The protection is also active for negative (reverse) active power, but it is
independent of the RP protection (Protection against reverse active power).
Summary table for G Touch protections
ABB
ANSI
(5)
Threshold
Tolerance
threshold
Tripping time
Calculation
formula t
t
(1)
Tolerance t
t
(2)
S(V)
(Step)
51V
I20 = 0.6...10 In; step = 0.1 In
(6)
Ul = 0.2…1 Un; step = 0.01 Un
Ks = 0.1…1; step = 0.01
(6)
± 10 %
t20 = 0.05…30 s
step = 0.01 s
t
t
= t20
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
S(V)
(3)
(Linear)
51V
I20 = 0.6...10 In; step = 0.1 In
(6)
Ul = 0.2…1 Un; step = 0.01 Un
(7)
Uh = 0.2…1 Un; step = 0.01 Un
(7)
Ks = 0.1…1; step = 0.01
(6)
± 10 %
t20 = 0.05…30 s
step = 0.01 s
t
t
= t20
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
RV 59N
U22 = 0.05….0.5 Un
step = 0.001 Un
± 5 %
t22 = 0.05…120 s
step = 0.01 s
t
t
= t22
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
RQ 40/32R
Q24 = -1…-0.1 Sn; step = 0.001
Sn
Kq = -2…2; step = 0.01
Vmin = 0.5...1.2 Un; step = 0.01
± 10 %
t24 = 0.5…100 s
step = 0.1 s
t
t
= t24
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
OP 32OF
P26 = 0.4…2 Sn
step = 0.001 Sn
± 10 %
t26 = 0.5…100 s
step = 0.5 s
t
t
= t26
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
OQ 32OF
Q27 = 0.4…2 Sn
step = 0.001 Sn
± 10 %
t27 = 0.5…100 s
step = 0.5 s
t
t
= t27
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
UP 32LF
P23 = 0.1...1 Sn
step = 0.001 Sn
± 10 %
t23 = 0.5…100 s
step = 0.5 s
t
t
= t23
The better of the two
values:
± 10 % or ± 40 ms (for a
time set < 5 s) / ± 100 ms
(for a time set > 5 s)
Continued on the next page