EasyManua.ls Logo

ABB SACE Emax E4.2 - Disassembly Operations for Circuit Breakers E2.2-E4.2-E6.2

ABB SACE Emax E4.2
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ABB | SACE Emax 2
30 | © 2018 ABB | 1SDH001316R0002 - ECN000086018 - Rev. C Accessories | 1 - Preliminary considerations
Disassembly operations for
circuit breakers E2.2-E4.2-E6.2
To dismantle the accessories, the following parts must be removed from the circuit-breaker:
Transparent flange (A) of the trip unit, by turning the screws (B).
Front cover of the circuit-breaker (C), by removing the mounting screws (D).
A
D
B
C
2
1
90°
1
2
Figure 9 - Removing the flange and front cover
After reassembling the accessories, the parts previously dismantled must be reassembled as indicated:
Front cover of the circuit-breaker (C), by screwing in the mounting screws (D) with tightening torque 1.1
Nm - 9.74 lb in.
Transparent flange (A) of the trip unit, by turning the screws (B).
A
D
B
C
1
90°
2
1
2
Figure 10 - Assembly of flange and front cover
8mm
0.5 2.5mm
2
2
1
0.5 1.5mm
2
20 AWG16AWG
20 AWG14AWG
Max O 3.3m
m
Max
O.301 "
Max O 3.3m
m
Max
O.301 "
0.31"
8mm
0.31"
Figure 11 - Wiring with cable stripping and relevant cross-sections