25
Measured value Code Data Value
direction
Remote resetting of recorded data V102 W 1 = resetting
Remote control of setting V150 R,W 0 = main settings active
1 = second setting active
Event mask for stage 1 V153 R,W 0...63, see "Event codes"
Event mask for stage 2 V154 R,W 0...63, see "Event codes"
Event mask for stage 3 V155 R,W 0...63, see "Event codes"
Event mask for stage 4 V156 R,W 0...63, see "Event codes"
Event mask for output signals V157 R,W 0...255, see "Event codes"
Event mask for output relays V158 R,W 0...255, see "Event codes"
Event mask for recovery function V159 R,W 0...31, see "Event codes"
Opening of password V160 W 1...999
Changing or closing of password V161 W(P) 0...999
Activation of self-supervision system V165 W 1 = self-supervision
activated and IRF LED is lit
EEPROM formatting V167 W(P) 2 = formatting
Address of relay module V200 R,W 1...254
Data transfer rate V201 R,W 4800 or 9600 Bd
Program version V205 R 131_
Reading of event register L R Time, channel number
and event code
Re-reading of event register B R Time, channel number
and event code
Type designation of relay module F R SPCF 1D15
Reading of relay module status data C R 0 = normal status
1 = module been subject to
automatic reset
2 = overflow of event register
3 = events 1 and 2 together
Resetting of module status data C W 0 = resetting
Reading and setting of time T R,W 00.000...59.999
The event register can be read only once using
the L code. Should a fault occur, say, in the data
transfer, the B command can be used to re-read
the contents of the register. When required, the
B command can be repeated. In general, the
control data communicator reads the event data
and forwards the information to an output de-
vice. Under normal conditions the event regis-
ter of the relay module is empty. The control
data communicator also resets abnormal status
data, so this data is normally zero.
Control parameters