5 - 2 WBPEEUI240774A0
Status LEDs
Status LEDs
The IMASI23 module has two LEDs, one red and one green,
that show its operating status.
Red flashes on power up.
Both remain off after passing onboard diagnostics until the
ASI module is configured by the controller.
Green is solid after the controller downloads configuration
data.
Green is solid during normal running.
Blinking green when the controller that configured the ASI
module enters configure mode from execute mode.
Blinking green if I/O expander bus communication is lost
(if the controller is removed).
Red is solid if a fatal failure of the ASI module occurs. For
example, if power up diagnostics fail.
Red is solid for a power fail interrupt (PFI).