EasyManua.ls Logo

ABB TX series - LIQUID FLOW JP3 Jumper Configuration; LEVEL OR AIR FLOW JP3 Jumper Configuration; TEMPERATURE JP3 Jumper Configuration

ABB TX series
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating instruction manual | TX Thermal Disperson Level Switches 9
LIQUID FLOW (BOTTOM BOARD)
JP3 Jumper Conguration
CONDITION State A State B
Relay Energized LED On
Fail Safe
Flow > Set-Point
Normal Condition
Flow < Set-Point
Normal Condition
Relay De-energized LED OFF Flow < Set-Point Flow > Set-Point
LEVEL OR AIR FLOW (BOTTOM BOARD)
JP3 Jumper Conguration
CONDITION State A State B
Relay Energized LED On
Fail Safe
WET or Air Flow > Set-Point
Normal Condition
DRY or Air Flow < Set-Point
Normal Condition
Relay De-energized LED OFF DRY or Air Flow < Set-Point
Normal Condition
WET or Air Flow > Set-Point
Normal Condition
TEMPERATURE (BOTTOM BOARD)
JP3 Jumper Conguration
CONDITION State A State B
Relay Energized LED On
Fail Safe
Temperature < Set-Point
Normal Condition
Temperature > Set-Point
Normal Condition
Relay De-energized LED OFF Temperature < Set-Point
Normal Condition
Temperature < Set-Point
Normal Condition
4.0 CONFIGURATION (cont’d)
2
4
1
3
1
3
2
4
1
3
2
4
1
3
2
4
2
4
1
3
2
4
1
3

Related product manuals