30-40kVA Power Terminal Positions
Maximum Current Table
Input/ Output
Voltage
Output Power
Maximum Input
Current
(1)
Max.
Output/Bypass Input
Current
(2)
Max. Battery
Discharge Current
(3)
200V
10kVA/10kW
33.8A
28.9A
70.4A
15kVA/15kW
50.2A
43.3A
105.0A
20kVA/20kW
67.2A
57.7A
140.0A
30kVA/30kW
100.8A
88.7A
191.8A
40kVA/40kW
134A
118.3A
255.8A
208 V
10kVA/10kW
32.5A
27.8A
70.4A
15kVA/15kW
48.3A
41.6A
105.0A
20kVA/20kW
64.6A
55.5A
140.0A
30kVA/30kW
96.6A
85A
191.8A
40kVA/40kW
128.6A
113.4A
255.8A
220 V
10kVA/10kW
30.7A
26.2A
70.4A
15kVA/15kW
45.6A
39.4A
105.0A
20kVA/20kW
61.1A
52.5A
140.0A
30kVA/30kW
91.3A
80.3A
191.8A
40kVA/40kW
121.5A
107.1A
255.8A
(1) The UPS is operating at rated voltage, rated power and batteries are charging but regardless of the overload.
(2) The UPS is operating at rated voltage and rated power but regardless of the overload.
(3) 12Vbattery blocks × 16pcs. The UPS is operating at rated voltage and rated power but regardless of the overload.