41
Communication Slot1
This slot can will accept a Relay card or RS-485 MODBUS card.
Communication Slot2
This slot will accept a Relay card or SNMP card. Always ensure that the SW2 switch is in
the correct position when this slot is used.
Batt. Temp.--External battery temperature connector
Connect to external battery temperature sensor. Please refer to section 5-4.
RS-232
Pin Assignment:
1 2 3 4 5
6 7 8 9
Baud Rate
57600bps
Data Length
8 bits
Stop Bit
1 bit
Parity
None
This port is available for changing the settings of the UPS by setting software.
Paral-1&Paral-2—Parallel communication port
Parallel communication cables are required to connect 2 or more UPSs' to each other in
order to operate in parallel. Refer to section 2-7for detail connections.
H↔U—communication selector
This switch is to select HMI or USB port. This switch must be in the “H” position in order
for HMI port is function.
Default Definition
General alarm
OUT-1
Load on inverter
OUT-2
Load on Bypass
OUT-3
Normal mode
IN
2TX (OUT)
3RX (IN)
5Ground