17
COMMISSIONING
Adjust the opening speed.
Minimum safe opening and closing times for door of various widths and weights are
summarized in the table.
Hold open times
Adjust fi rst hold open time for delayed impulse and then hold open time for normal impulse.
Adjusting the hold open time for delayed impulse
Entering the mode:
• Turn mode switch to AUTO position.
• Press TEACH button at least 3 seconds.
• In the programming mode green led is lit, yellow led is fl ashing 3 times, pause, 3 times,
pause...
• Adjust the hold open time for delayed impulse (0...60 sec). Time starts when the door is in
open position. Full right position (seq) of the potentiometer means that every other impulse
either opens or closes the door.
Back to normal mode:
• Press TEACH button at least 3 seconds or wait 2 minutes.
• Turn mode switch to MAN position.
Adjusting hold open time for normal impulse
Adjust the hold open time (0...60 s). Time starts when the door is in open position. Full right
position (seq) of the potentiometer means that every other impulse either opens or closes the
door.
Note! For safe operation, always use low force, speed and long hold open time.
10 Test the operation
• Turn mode switch to AUTO.
• Test the operation
• If the function is not desired, repeat steps 4 to 9.
Resetting operator to factory settings (operator is moved to new door)
• Turn mode switch to OPEN.
• Push TEACH-button briefl y. After that push TEACH-button 5 sec.
Door open and closed position information is removed from the memory.
SPEED
min max
HOLD
OPEN
seq
0
60
HOLD
OPEN
seq
0
60
Time (sec.) Door weight (kg)
60 80 100 120
Door
width
(mm)
800
1000
1200
1300
2,7 3,2 3,5 3,9
3,4 4,0 4,4 4,8
4,1 4,7 5,3 5,8
4,5 5,1 5,8 6,3