22
FS
ON
12345678
ON Kill input not in use
OFF When kill is activated, the door will close immediately if not already closed.
Hold open and low pass filter timers are reset.
ON Lockcase locked without power.
OFF Lockcase locked with power.
ON The lock activation time is until door closing.
OFF The lock activation time is 1,5 s + (opening delay).
.
OFF OFF
ON OFF
TB2:11 and 13
TB2:11 and 13
OFF AUTO
TB2:11 and 13
TB2:11 and 13
AUTO OFF
TB2:11 and 13
TB2:11 and 13
OFF OPEN DOOR
TB2:11 and 13
TB2:11 and 13
OPEN DOOR OFF
ON ON
OFF ON
DIP -switches FS
FS1 Kill input
FS2 and FS3 Operation mode without program switch
MVI impulse accepts a potential-free contact or 6-24 V AC/DC. Status of lock (operation
mode) can be selected via a function selector FS2 and depends on input TB2:11 and 13.
In AUTO mode, the lockcase is open and opening delay is not in use.
FS2 FS3
FS4 Lock type
FS5 Activation time for lockcase