EasyManuals Logo

Acrel ACR10R Series User Manual

Acrel ACR10R Series
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
`
- 27 -
energy in January
points
1252-1253
Historical active peak electric
energy in January
RO
Same as above
2
1254-1255
Historical active flat electric
energy in January
RO
Same as above
2
1256-1257
Historical active trough electric
energy in January
RO
Same as above
2
1258-1259
Historical total active electric
energy in January
RO
Same as above
2
1260-1269
Historical active electric energy
in February
RO
Same as above
10
1270-1279
Historical active electric energy
in March
RO
Same as above
10
1280-1289
Historical active electric energy
in April
RO
Same as above
10
1290-1299
Historical active electric energy
in May
RO
Same as above
10
1300-1309
Historical active electric energy
in June
RO
Same as above
10
1310-1319
Historical active electric energy
in July
RO
Same as above
10
1320-1329
Historical active electric energy
in August
RO
Same as above
10
1330-1339
Historical active electric energy
in September
RO
Same as above
10
1340-1349
Historical active electric energy
in October
RO
Same as above
10
1350-1359
Historical active electric energy
in November
RO
Same as above
10
1360-1369
Historical active electric energy
in December
RO
Same as above
10
1370-1379
Total active electric energy
RO
Same as above
10
2000-2061
Phase A voltage 2-63 harmonic
content
RO
Phase A voltage 2-63 harmonic; decimal
points: 2
62
2062-2123
Phase B voltage 2-63
harmonic content
RO
Phase B voltage 2-63 harmonic; decimal
points: 2
62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Acrel ACR10R Series and is the answer not in the manual?

Acrel ACR10R Series Specifications

General IconGeneral
ModelACR10R series
CommunicationRS485, Modbus-RTU
ProtectionIP20
DisplayLCD
Power SupplyAC/DC
Rated CurrentAC 1A, AC 5A
Frequency45Hz - 65Hz
Accuracy class0.5
Power consumption<5VA
Operating temperature+55°C
Storage temperature-25℃~+70℃
SafetyIEC/EN 61010-1
EMCIEC 61326-1
Relative Humidity≤95% (non-condensing)
Voltage overload1.2x rated voltage continuously, 2x rated voltage for 1 second

Related product manuals