EasyManuals Logo

Acrel ADL400 User Manual

Acrel ADL400
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
- 6 -
如:U = 220.1Vf = 49.98Hz, I = 1.99AP = 0.439kW
Such as:U = 220.1Vf = 49.98Hz, I = 1.99AP = 0.439kW
7.2
计量功能
Calculating
能计量当前组合有功电能,正向有功电能,反向有功电能,正向无功电能,反向无功
能。
Can measure the active energyreversing active energyforward reactive energyreversing
reactive energy
7.3
分时功能
Timing
两套时段表,一年可以分为 4 个时区每套时段表可 14 个日时段,4 个费率(F1F2
F3F4 即尖峰平谷)
Two timing tablefour time zoneone table have fourteen timingfour rate
7.4
需量功能
Demand
有关需量的相关概念如下:
The description about demand:
3 需量概念表
Table 3 Demand description list
Demand
需量周期内测得的平均功率叫需量
The average power in the demand cycle.
最大需量
Maximum
demand
在指定的时间区内需量的最大值叫最大需
The maximum value of demand in a period of time.
滑差时间
Slip time
从任意时刻起,按小于需量周期的时间递推测量需量的方法,
所测得的需量叫滑差式需量。递推时间叫滑差时间。
From any time, the method of measuring demand recursively
according to the time less than the demand period is called slip
demand.The recurrence time is called slip time.
需量周期
Demand
cycle
连续测量平均功率相等的时间间隔, 也叫窗口时间
The time period between two same average value of demand.
缺省需量周期 15 分钟,滑差时间为 1 分钟
能测量 4 种最大需量即正向有功、反向有功、感性无功容性无功最大需量以及最大需
量发生的时间
The default demand cycle is 15 minutes, slip time is 1 minute.
The meter can measure 4 kinds of maximum demand: forward active, reversing active,
inductance reactive, capacitance reactive maximum demand and the occur time.
7.5
历史数据统计功
History data statistics
能统计上 48 月的历史电能(各费率电能)和上 90 日的历史电能(各费率电能)。
The meter can record last 48 months or last 90 days history energy in each tariff.