- 31 -
Bit0:A 相过压;
Over-voltage on A phase
Bit1:B 相过压;
Over-voltage on B phase
Bit2:C 相过压;
Over-voltage on C phase
Bit3:A 相失压;
Lose-voltage on A phase
Bit4:B 相失压;
Lose-voltage on B phase
Bit5:C 相失压;
Lose-voltage on C phase
Bit6:A 相逆向;
Reversing on A phase
Bit7:B 相逆向;
Reversing on B phase
Bit8:C 相逆向;
Reversing on C phase
Bit9:A 相电流过高;
Over current on A phase
Bit10:B 相电流过高;
Over current on B phase
Bit11:C 相电流过高;
Over current on C phase
Bit12:A 相电流过低;
Low current on A phase
Bit13:B 相电流过低;
Low current on B phase
Bit14:C 相电流过低;
Low current on C phase
如当前仪表地址为 001,读取上 1 条事件记录主站发送:01 03 30 01 00 06
9B 08,从站回复为 :01 03 0C 12 01 08 0A 01 01 (18 年 1 月 8 日 10 时 1
分 1 秒)01 00(上电) 00 00(上电事件无事件详情) 00 00(预留) 80 23。
Example: The address is 001 at present, and we send the code: 01 03 30 01 00 06
9B 08 to get the last event record, and the slave station will give back: 01 03 0C 12 01
08 0A 01 01(2018/1/8 10:1:1)01 00(powered)00 00(no details)00 00(reserved)
80 23