- 20 -
00CAH
背光时间 The back light time
2
R/W
0-255 分钟,大于 250
常亮
0-255minutesmore
than 250 stay light-on
00CBH-0120H
保留 Reserve
0121H
日冻结时间:
Daily frozen time:Hour
2
R/W
0122H
月冻结:日、时
Monthly frozentime:dayhour
2
R/W
0123H-0163H
保留 Reserve
0164H
A 相有功功 Active power of A phase
4
R
补码形式
分辨率:0.001kW
Complement form
Resolution0.001kW
0166H
B 相有功功 Active power of B phase
4
R
0168H
C 相有功功
Active power of C phase
4
R
016AH
总有功功率
Total active power
4
R
016CH
A 相无功功
Reactive power of A phase
4
R
补码形式
分辨率:0.001kvar
Complement form
Resolution0.001kvar
016EH
B 相无功功
Reactive power of B phase
4
R
0170H
C 相无功功
Reactive power of C phase
4
R
0172H
总无功功率
Total reactive power
4
R
0174H
A 相视在功
Apparent power of A phase
4
R
补码形式
分辨率:0.001kVA
Complement form
Resolution0.001kVA
0176H
B 相视在功
Apparent power of B phase
4
R
0178H
C 相视在功
Apparent power of C phase
4
R
017AH
总视在功率 Total apparent power
4
R
017CH-017FH
保留 reserve
0180H
当日正向有功最大需量
Maximum forward active demand a day
2
R
分辨率:0.001
发生时间:分、时
0181H
发生时间:分、时
Occur time:minute、hour
2
R
0182H
当日反向有功最大需量
Maximum reversing active demand a day
2
R
0183H
发生时间:分、时
Maximum reversing active demand a day
2
R
0184H
当日正向无功最大需量
Maximum forward reactive demand a day
2
R
0185H
发生时间:分、时
Occur time:minute、hour
2
R
0186H
当日反向无功最大需量
2
R
0187H
发生时间:分、时
2
R