Table 6‑1. Using LED states for troubleshooting
Troubleshooting
Check
Action
Is the green ON/
READY LED lit?
If no: The auxiliary 230 VAC or 24 VDC supply is faulty.
Is the red ON/
READY LED lit?
If yes: There is an EEPROM fault.
Is the red ON/
READY LED
blinking?
If yes: The hardware configuration is incorrect.
Is the orange ON/
READY LED
blinking?
If yes: The firmware is being updated.
Is the red LIMIT
LED lit?
If yes: The unit is unable to supply enough power to match the
setpoint due to a limiting condition. When an internal
protection limit is exceeded, the output is limited but not shut
off.
1. Disable the output.
2. Verify that the limitation setting is correct.
3. Verify that the unit load and load connections are correct.
Is the FAULT LED
lit?
If yes: The unit has detected a fault. This fault will generate
error data that can be viewed using the ThyroTouch display
or the Thyro-Tool Pro software.
Are any red
CONTROL LEDs
lit?
If yes: The unit has a fault in the corresponding power section.
TROUBLESHOOTING UNIT OUTPUT
Use extreme caution when troubleshooting the unit output.
  DANGER:
RISK OF DEATH OR BODILY INJURY. Disconnect and lockout/tagout all
sources of input power before working on this unit or anything connected to
it.
Advanced Energy
®
Thyro-PX
®
Power Controller
57010148-00G Troubleshooting and Global Services 6‑2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advanced Energy Thyro-PX 3PX and is the answer not in the manual?

Advanced Energy Thyro-PX 3PX Specifications

General IconGeneral
BrandAdvanced Energy
ModelThyro-PX 3PX
CategoryController
LanguageEnglish

Related product manuals