What to do if my Advanced Energy Thyro-PX has no load current?
- SsarahadamsAug 5, 2025
If your Advanced Energy Controller shows no load current, verify the following: * The supply voltage of the A70 control device is within the range of 90 VAC to 265 VAC, or X3.1 and X3.2 are at 24 VDC. * The setpoint is available and active. Check the total setpoint (effective total) using the display or software, or measure the setpoint on X52.2 and X52.5. * Parameters of the control characteristic of the respective analog input are correct. * For 1PX and 2PX units, verify that the reference phase is connected. Also, check if parameters Iemax, Uemax, and Pmax are set too small, or if controller parameters Ti or Kp are set too large. For type 1PX, check if the load is broken or disconnected.



