EasyManuals Logo

Advanced Energy Thyro-PX Series User Manual

Advanced Energy Thyro-PX Series
109 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
Installation, Setup, and
Operation
PREPARING TO INSTALL THE UNIT
Spacing Requirements
Install the unit in a vertical orientation to ensure that thyristors attached to heat sinks
are adequately ventilated. If you intend to mount this unit in a cabinet, ensure that the
cabinet itself is adequately ventilated, and that the following requirements are met.
The minimum distance between the bottom of the unit and the bottom of the
cabinet or any other object is 100 mm (4″).
The minimum distance between the top of the unit and the top of the cabinet or
any other object is 150 mm (6″).
The minimum distance between the top of the unit and the bottom of another
unit is 150 mm (6″).
Units may be installed side-by-side with no intervening distance.
Ensure that the unit is not exposed to sources of heat.
Dimensional Drawings
The following figures show Thyro-PX unit dimensions, front, and side views.
Thyro-PX
®
Power Controller
Chapter
5
57010148-00G Installation, Setup, and Operation 5‑1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advanced Energy Thyro-PX Series and is the answer not in the manual?

Advanced Energy Thyro-PX Series Specifications

General IconGeneral
BrandAdvanced Energy
ModelThyro-PX Series
CategoryController
LanguageEnglish

Related product manuals