PREPARING TO INSTALL THE UNIT
Spacing Requirements
Install the unit in a vertical orientation to ensure that thyristors attached to heat sinks
are adequately ventilated. If you intend to mount this unit in a cabinet, ensure that the
cabinet itself is adequately ventilated, and that the following requirements are met.
The minimum distance between the bottom of the unit and the bottom of the
cabinet or any other object is 100 mm (4″).
The minimum distance between the top of the unit and the top of the cabinet or
any other object is 150 mm (6″).
The minimum distance between the top of the unit and the bottom of another
unit is 150 mm (6″).
Units may be installed side-by-side with no intervening distance.
Ensure that the unit is not exposed to sources of heat.
Dimensional Drawings
The following figures show Thyro-PX unit dimensions, front, and side views.