EasyManua.ls Logo

Advanced Energy Thyro-PX Series - Figure 5-27. Primary VSC; Figure 5-28. Secondary VSC

Advanced Energy Thyro-PX Series
109 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Primary VSC is particularly suitable for large load currents (I
Load
> I
Controller
) with
smaller voltages. One transformer is used for each load. The following illustrations
show the two stage and three stage VSC connections. Details can be found in the
Thyro-PX VSC connection diagrams, Figure 530 and Figure 531.
  CAUTION:
In the primary VSC configuration, the mains voltage is stepped up on the
inactive power controller outputs, marked * in the following figure. The
transformer must be designed so that this voltage does not exceed the type
voltage (500 V or 690 V) of the unit, or the unit will be damaged.
  ATTENTION:
Dans la configuration principale de VSC, la tension de l'alimentation secteur
est élevée sur les sorties du contrôleur de puissance inactive, indiqué par *
dans l'illustration suivante. Le transformateur doit être conçu de façon à ce
que la tension n'excède par la tension type de l'appareil (500 V ou 690 V);
autrement l'appareil pourrait être endommagé.
Mains MainsTransformer Transformer
Load
Load
Primary VSC 2 Primary VSC 3
Figure 5‑27. Primary VSC
Secondary VSC is particularly suitable if many heaters are being supplied from one
transformer. Through the improvement of the power factor, a larger transformer can
dispense more active power and supply additional loads (if required).
Mains
Mains
Transformer Load
Secondary VSC 3
Secondary VSC 2
Load
Transformer
Figure 5‑28. Secondary VSC
Advanced Energy
®
Thyro-PX
®
Power Controller
57010148-00G Installation, Setup, and Operation 5‑24

Table of Contents

Related product manuals