1.4 RS232 Serial Interface
The connection to the PC Configuration Tool is
via a serial RS232 connector as tabled below.
GND
RX
TX
Terminal
Function
GND (0V)
RS232 ground reference
TX
RS232 Transmit data to external BMS system
RX
RS232 Receive data from BMS system
1.5 10 Base-T Ethernet Port
Connect a standard straight through RJ45 Ethernet cable to an existing LAN or router.
Note: Before connecting to an existing LAN, IP addressing information from the network
administrator will be required.
1.6 Commissioning the Interface
Each interface must have a unique network node address. See also the Ad-Net Technical Document (Document
number 680-502) for detailed information on how to set-up and commission networks.
1.7 Default Settings
The following factory default settings are used, but these can be changed as required.
Network Node 50
Next Node 1
Interface Zone 200
RS232 Baud Rate 38400
IP Address 0.0.0.0
Subnet Mask 255.255.255.0
Gateway 0.0.0.0
TCP Port ** 80
SMTP Server 0.0.0.0
Email Address “”
SMTP User “”
SMTP Password “”
Administrator Password admin
User Password user
Remote Access Level FULL ACCESS
Consent Timeout 0 Seconds
** The TCP Port is actually a fixed setting and is presented for information purposes.
Note that if multiple ipGateway interfaces, or other network interfaces, with the same default settings are used it
is essential to change the defaults to give unique parameters for each interface.