1 Introduction
Four relay outputs are provided. These can be independently programmed with different cause and effect rules.
The outputs can be configured to turn ON only.
The PC CONFIG tool is used to program the presence and functionality of these outputs. By default, the outputs
cannot be silenced. The outputs can be configured to follow investigation delays, allow silence and be inverted,
if required.
When “All Other Outputs” are disabled at the panel, all relay outputs attached to the panel are disabled. Outputs
can also be individually disabled via the user menus or disabled using the group disable function through
programming.
The Boxed unit is provided with a power supply. Status indications for Power and Fault are provided.
On-board indicators are provided for each relay output (illuminated when the relay is activated), Bus
communications Transmit TX and Receive RX and a Heartbeat indicator (flashes at a rate of 1Hz to show
normal operation and at a rate of 5Hz to show an internal fault condition).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advanced MxPro Series and is the answer not in the manual?

Advanced MxPro Series Specifications

General IconGeneral
Product RangeAdvanced MxPro Series
Vibration Resistance10-55Hz, 1.5mm amplitude
Contact FormSPDT
Operating Voltage24V DC
Coil Voltage24V DC
Operate Time10ms
Release Time5ms
Insulation Resistance1000MΩ
Ambient Temperature+70°C
Dielectric Strength2500V AC

Related product manuals