WEEKLY TEST
The call point test key should be inserted firmly and deliberately into the bottom of the manual call point.
Once activated it may be necessary to wait up to four seconds before the alarms sound.
Your manual call points may not be the same as the ones described above. If not please refer to your service
and maintenance company for instructions.
Note:
Before testing the fire alarm system it may be necessary to isolate ancillary outputs.
It is essential that any alarm receiving centre is contacted immediately before and immediately after, the weekly
test to ensure that unwanted alarms are avoided and that fire alarm signals are correctly received at the alarm
receiving centre.