Chapter 4 Command Set 4-27
Chapter 4
ADAM-4051 Command Set Table
Note: For command sets and further application, please link to
Advantechs web site to download the latest ADAM-4000
users manual and Windows Utility.
1)Link to http://www.advantech.com
2)Click Support to get in eService Knowledge Center
3)Search for download and key-in ADAM-4000 to get the latest
ADAM-4000 Users Manual
Command Syntax Command Name Command De s cription Page No.
%AANNTTCCFF Configuration
Sets the address, baud rate, and/or
checksum status to a digital I/O module
4-152
#**
Synchronized
Sampling
Orders all digital I/O modules to sample
their input values and store them in special
registers
4-158
$AA2
Configuration
Status
Returns the configuration parameters of a
sp ecified digital I/O mod ule
4-161
$AA4
Read
Synchronized Data
Returns the value of a specified digital I/O
module that was stored in the specified
register after an #** command was issued
4-159
$AA5 Reset Status
Indicates whether a specified digital I/O
module was reset after the last time that
$AA5 command was issued
4-163
$AA6 Digital Data In
Returns the values of the digital I/O
channel in the addressed module
4-154
$AAF
Read Firmware
Versi on
Return the firmware version code from the
sp ecified digital I/O mod ule
4-165
$AAM
Read Module
Name
Return the module name from the specified
digital I/O module
4-166

Table of Contents