EasyManuals Logo

Advantech Adam 4000 Series User Manual

Advantech Adam 4000 Series
398 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #187 background imageLoading...
Page #187 background image
Chapter 4 Command Set 4-103
Chapter 4
Command
Syntax
Command
Name
Description I/O Module
@AADI Read Digital I/O
and Alarm
Status
The addressed module returns
the state of its digital input and
digital output channels and the
status of its alarm
4011, 4011D, 4012,
4014D, 4016
@AADO(data) Set Digital
Output Values
Set the values of the modules
digital outputs (ON or OFF)
4011, 4011D, 4012,
4014D, 4016
@AAEAT Enable Alarm Enables the alarm in either
Momentary or Latching mode
4011, 4011D, 4012,
4014D, 4016
@AAHI(data) Set High Alarm
Value
Downloads the High alarm limit
value
4011, 4011D, 4012,
4014D, 4016
@AALO(data) Set Low Alarm
Value
Downloads the Low alarm limit
value
4011, 4011D, 4012,
4014D, 4016
@AADA Disable Alarm Disables all alarm functions 4011, 4011D, 4012,
4014D, 4016
@AACA Clear Latch
Alarm
Resets the modules Latch
alarm to zero
4011, 4011D, 4012,
4014D, 4016
@AARH Read High
Alarm Value
Ask the addressed module to
return its high alarm value
4011, 4011D, 4012,
4014D, 4016
@AARL Read Low Alarm
Value
Ask the addressed module to
return its low alarm value
4011, 4011D, 4012,
4014D, 4016
@AARE Read Event
Counter
Ask the addressed module to
return its event counter value
4011, 4011D, 4012,
4014D
@AACE Clear Event
Counter
Reset the modulesevent
counter to zero
4011, 4011D, 4012,
4014D
4.4.4 Digital I/O, Alarm and Event Command Set

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam 4000 Series and is the answer not in the manual?

Advantech Adam 4000 Series Specifications

General IconGeneral
BrandAdvantech
ModelAdam 4000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals