Chapter 4 Command Set 4-59
#**
Name Synchronized Sampling
Description Orders all analog input modules to sample their input values
and store the values in special registers.
Syntax #**
# is a delimiter character.
** is the actual synchronized sampling command.
The terminating character, in the form of a carriage return (0Dh),
is not required.
Response The analog input modules will send no response after executing
the synchronized sampling command. In order to retrieve the
data, a separate Read Synchronized Data command has to be
issued for every analog input module.
The pound sign (#) followed by two asterisks (**) does not represent an
optional value, but is the actual command string.
4011, 4011D, 4012, 4013, 4015,
4016, 4019