Chapter 4 Command Set 4-181
4080, 4080D
Chapter 4
$AAA
Name Read Gate Mode.
Description Request the specified counter/frequency module to return its
gate status.
Syntax $AAA(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of counter/frequency that you want to interrogate.
A identifies the Read Gate Mode command.
(cr) is the terminating character, carriage return (0Dh)
Response !AAG(cr) if the command is valid.
There is no response if the module detects a syntax or commu-
nication error, or if the specified address does not exist.
! is a delimiter character indicating the command was valid.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter/frequency module.
G determines the gate mode.
G = 0 the gate is low
G = 1 the gate is high
G = 2 the gate is disabled.
(cr) is the terminating character, carriage return (0Dh).
Example command: $01A(cr)
response: !011(cr)
The command requests the addressed counter/frequency
module to return its gate status. The module at address 01
replies that its gate is high.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam 4000 Series and is the answer not in the manual?

Advantech Adam 4000 Series Specifications

General IconGeneral
BrandAdvantech
ModelAdam 4000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals