Chapter 4 Command Set 4-197
4080, 4080D
Chapter 4
$AA1H
Name: Read Non-isolated High Trigger Level.
Description: Read the high trigger level for non-isolated input signals of a
specified counter/frequency module.
Syntax: $AA1H(cr)
$ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of counter/frequency module that you want to interro-
gate.
1H identifies the Read Non-isolated High Trigger Level
(cr) is the terminating character, carriage return (0Dh)
Response: !AA(data)(cr) if the command is valid.
?AA(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exists.
! is a delimiter character indicating the command was valid.
? is a delimiter character indicating the command was invalid.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter/frequency module.
(data) is the high trigger level of non-isolated input signals
The unit and resolution are both 0.1 V (voltage). The format is
a two digit integer that can range from 1 to 50 ( i.e. 0.1 V to 5
V ).
(cr) is the terminating character, carriage return (0Dh).
Example: command: $131H(cr)
response: !1330(cr)
The command requests the counter/frequency module at
address 13 to read its non-isolated high trigger level. The
addressed module replies that the high trigger level is 3 V.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam 4000 Series and is the answer not in the manual?

Advantech Adam 4000 Series Specifications

General IconGeneral
BrandAdvantech
ModelAdam 4000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals