4-208 ADAM 4000 Series User's Manual
4080
Command Set
@AARP
@AARA
Name Read Alarm Limit Value of Counter 0 (or 1)
Description Read the alarm limit value of counter 0 (or 1) of the specified
counter module at address AA.
Syntax @AARP(data)(cr)
@AARA(data)(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
RP represents the Read Alarm Limit Value for counter 0
command.
RA represents the Read Alarm Limit Value for counter 1
command.
(cr) is the terminating character, carriage return (0Dh).
Response !AA(data)(cr) if the command is valid.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
! is a delimiter character indicating a command was valid.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
(data) is the alarm limit value which must consist of eight
hexadecimal digits.
(cr) is the terminating character, carriage return (0Dh).
Example command: @12RP(cr)
response: !120000FFFF(cr)
The command instructs the module at address 12h to return the
alarm limit value of counter 0. The module replies that the alarm
limit value of counter 0 is 0000FFFF.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam 4000 Series and is the answer not in the manual?

Advantech Adam 4000 Series Specifications

General IconGeneral
BrandAdvantech
ModelAdam 4000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals