4-218 ADAM 4000 Series User's Manual
4080
Command Set
@AARA
Name Read High-alarm Count Value for Counter 0.
Description Requests the addressed counter module to return its high-alarm
count value of counter 0.
Syntax @AARA(cr)
@ is a delimiter character.
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
RA identifies the Read High-alarm Count Value command
(cr) is the terminating character, carriage return (0Dh)
Response !AA(data)(cr) if the command is valid.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exists.
! a delimiter character indicating a valid command
AA (range 00-FF) represents the 2-character hexadecimal
address of a counter module.
(data) is the high-alarm count value which consists of eight
hexadecimal digits.
(cr) is the terminating character, carriage return (0Dh).
Example command: @12RA(cr)
response: !12F0000000(cr)
The command instructs the module at address 12 to return its
high-alarm count value. The module replies that counter 0's
high-alarm count value is F0000000(hex).
4080D

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Advantech Adam 4000 Series and is the answer not in the manual?

Advantech Adam 4000 Series Specifications

General IconGeneral
BrandAdvantech
ModelAdam 4000 Series
CategoryControl Unit
LanguageEnglish

Related product manuals