5.11 International Calling/Texting
The system can call/text international numbers, however the exit code should not be
specified and should be replaced with the ‘+’ symbol e.g:
UK Number 07574163367 should be entered as +447574163367 when outside the UK
5.12 Dial Now
If necessary the system can make a call to a number not stored in it’s memory at any
time. This is achieved using the DIAL command. The call observes the RTIME, CTIME and
SILENCE time settings
DIAL<space>number. make an ad-hoc call to the specified number
e.g. dial 01517283167.
The call will end when the other party hangs up or the CTIME or SILENCE time limit is
reached.
5.13 Input Hold-off Time
Dialling and SMS sending can be delayed from 1 second to up to 500 minutes (over 8
hours) on any input using the HOLD command. Additionally after sending the SMS mes-
sage/dialling the call numbers the system can repeat the action after the delay time
again if required.
To set up the hold-ff time the following SMS text is sent to the system;
HOLD 10 10s delay on Input A
HOLDA R10 10s delay on Input A; repeat every 10s
HOLDB R120m. 120 minute delay on Input B; repeat every 120 mins (2 hours)
Holdc 2s 2 second delay on Input C
hold1 0 turn off delay on analogue input 1 (set delay time to zero)
NB. If the input is not specified then the default input is Input A
5.14 Repeating the SMS/Call
Dialling and SMS sending can be repeated after a user specified period from 1 second to
up to 500 minutes (over 8 hours) on any input using the REPEAT command. The call is
made/SMS sent immediately on the input becoming active and is repeated after the
time specified.
repeatA 10m. resends input A SMS/restarts dialling after 10 minutes
Repeat1 120. resends analogue channel 1 SMS/restarts dialling after 120s
5.15 Silencing the Alarm
The bell –ve wire can be routed through the relay COM and NC terminals onto the bell.
This allows the relay to break the connection when active and silence the alarm. Whilst
the bell is sounding the SILENCE command can be used to silence the bell. The connec-
tion is re-established once both inputs return to the idle state (i.e. the alarm panel is reset)
silence activates the output relay until the inputs are idle