2/2/4!ئ٪
ୟഗࢅ؏ݣዃሞᇱ๔ԈጎాLj٪ݣሞൣলĂ߅
ሳتă
BREAKER
ୟഗ
IP54 Covers:
Each ME09 breaker is supplied with a Door Frame that provides the
installed device with an IP40 raƟng. OpƟonally an extra cover is
available providing an IP54 raƟng.
OperaƟons Counter:
Provides local record of the cumulaƟve number of complete
breaker closing operaƟons.
Cable Interlocking Devices:
A set of devices that are available for Įxed and/ or drawout
devices. They allow the interlocking of two or three ME09
breakers in Įxed or drawout paƩern. Each mdevice has two
parts, a factory mounted interlocking mechanisms and two or
more separately available cables.
Bell Alarm Contact:
A changeover contact that once ĮƩed to the breaker indicates if
the breakers has tripped on one of it's protecƟve funcƟons
(Electronic Trip Unit).
An interface on the Trip Unit front face allows a Manual or
AutomaƟc breakers reset. The Bell Alarm Contact will only
permanently change posiƟon when the Trip Unit is in Manual
mode. The Trip unit has a funcƟon (trip reason and event
logger ) that allows the user to establish why the breaker has
tripped.
Spring Charged and Ready to Close Contacts:
A breaker with electrical charging mechanism can be equipped
with one or two indicaƟon contacts.
The Įrst the Spring Charged Contact simply does as indicated
and is supplied with the standard Motor OperaƟng Mechanism.
The second, the ready to close indicaƟon, opƟonally replaces
the Spring Charged Contact.
It only moves posiƟon when the following condiƟons are met:
- The circuit breaker is open
- The closing springs are charged
- The circuit breaker is not locked/interlocked in open posiƟon
- There is no standing closing order
- There is no standing opening order
Both contacts have a 1NO conĮguraƟon.
1.1.3 Storage
Store circuit breakers and casseƩes in a clean, dry locaƟon in
their original packaging.
NF1:ဣଚگუഘୟഗ