2.3 SPECIFICATIONS
Power type rating
Protect B.500 500 VA (cos φ = 0.7 lag.) 350 W
Protect B.750 750 VA (cos φ = 0.6 lag.) 450 W
Protect B.1000 1000 VA (cos φ = 0.7 lag.) 700 W
Protect B.1500 1500 VA (cos φ = 0.6 lag.) 900 W
UPS input 1 ph~ / N / PE
Nominal input voltage 220 / 230 / 240 V AC
Voltage range
without battery
mode
176 / 184 / 192 VAC 264 / 276 / 288 VAC
(depending on mains connection voltage)
Frequency
50 Hz / 60 Hz
(automatic detection)
Frequency tolerance range ±5%
Current consumption at 230 V AC, full load and battery charge (max.)
Protect B.500 2.7 A
Protect B.750 3.9 A
Protect B.1000 6.1 A
Protect B.1500 7.6 A
Connection Cold device plug
UPS output
Nominal output voltage /
AVR technology
220 V AC / 230 V AC (default) / 240 V AC -
10% +6%
Nominal output voltage in
battery mode
220 V AC / 230 V AC (default) / 240 V AC -
10% +5%
Frequency in battery mode
50 Hz / 60 Hz ±0.1
Hz
Nominal output current (at 230 V AC)
Protect B.500 2.1 A
Protect B.750 3.2 A
Protect B.1000 4.3 A
Protect B.1500 6.5 A
Switchover time in the event
of power failure
<10 ms
Voltage wave form Sinusoidal