vervoltage RJ11 (phone, fax, modem)
dataline protection RJ45 (Ethernet 10/100 MBit/s)
UPS Output
Rated output voltage
C.
1000 R (S) – C. 3000 R (S) 220 / 230 / 240 Vac ± 2 %
C.
6000 R 220 / 230 / 240 Vac ± 1 %
(configuration via software
“CompuWatch”)
Nominal frequency
C.
1000 R (S) – C. 3000 R (S) 50 Hz / 60 Hz ± 0.2 %
C.
6000 R 50 Hz / 60 Hz ± 0.1 %
(depending on mains)
Voltage waveform Pure sine wave
Harmonic distortion:
4 % THD (linear load)
7 % THD (non-linear load)
Connection Non-heating appliance connectors
Current Crest Ratio 3:1
Overload behaviour in battery mode
C.
1000 R (S) – C. 3000 R (S) up to 105 % ± 5 % continuous;
> 105 % ± 5 % – < 150 % ± 5 %
for 25 s;
150 % ± 5 % for 200 ms
C. 6000 R up to 105% continuous;
> 105 % for 10 s
Overload behaviour with existing mains
C.
1000 R (S) – C. 3000 R (S) up to 105 % ± 5 % continuous;
> 105 % ± 5 % – < 150% ± 5 %
for 30 s;
150 % ± 5 % for 300 ms
Then automatic inverter to
Bypass in < 4 ms (switches
back when overload damps =
Load < 90 %))