C. 6000
R up to 105 % continuous;
> 105 % – < 130 % for 10 min;
130 % for 1 s
Then automatic inverter to
Bypass in 0 ms (switches
back when overload damps
= Load < 90 %)
Short circuit behavior 3 x I
N
for 140 ms
Battery
Autonomy time (full load with internal battery)
PROTECT C. 1000 R 6 min.
PROTECT C. 2000 R,
C. 3000 R and C. 6000 R at least one battery module
required
Autonomy time with external optional battery expansions
(only for PROTECT C. – models):
Autonomy time (full load)
Coupled
battery modules
C.1000 R C. 2000 R C. 3000 R C. 6000 R
1 37 min. 10 min. 5 min. 8 min.
2 75 min. 30 min. 17 min. 25 min.
3 - 50 min. 30 min. 45 min.
4 - 75 min. 48 min. 60 min.
5 - 90 min. 60 min. 70 min.
Rated direct voltage (intermediate circuit)
PROTECT C. 1000 R (S) 36 V
PROTECT C. 2000 R (S) 96 V
PROTECT C. 3000 R (S) 96 V
PROTECT C. 6000 R 240 V
Battery charging current
PROTECT C. 1000 R 1 A
PROTECT C. 1000 R S 7 A
PROTECT C. 2000 R 1 A
17