32 23/05 – 4840212_00
Code Description Réarmement Eet Priorité Retard
Nombre de
tentatives
Période (s)
A29 Circuit 1 : pressostat de basse pression Param U081 Coupe le circuit 1 Grave circuit 1
Param. C049,
C050
3 3600
A30 Circuit 1 : surcharge du compresseur 1
M
Stop compr.1 Circ.1 Défaut de circuit 1 Non
- -