Electrical
m Make sure that power is OFF
before making any electrical connections!
m The operator is provided with two
knockout holes on each side. Run 1/2"
liquidtite flexible conduit through one of the
four knockout holes and into the handy box
where the receptacle is located. An elbow
fitting is attached to the handy box and a
straight fitting is supplied for the other end of
the flexible conduit. Run three 12 gauge
wires through the flexible conduit and into
the handy box. There should be a black or
other colored wire for hot, a white wire for
neutral, and a green wire for earth ground.
m Connect the three 12 gauge wires to
the 115 Volt receptacle.
m Connect the black (hot) wire to the
brass screw.
m Connect the white (neutral) wire to
the silver screw.
m Connect the green (ground) wire to
the green grounding screw.
m When the wires have been con-
nected to the receptacle, insert the recep-
tacle back into the handy box. Secure the
receptacle to the handy box with two screws.
Apply the receptacle cover to the receptacle
and secure it with a screw. The power cord
may now be plugged into the receptacle.
m If the gate operator is already factory
CONDUIT ROUTING
STANDARD 115 VOLT HOOK-UP