EasyManuals Logo

Airwell DLSE Series User Manual

Airwell DLSE Series
183 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
3-1
RATING CONDITIONS
SM DLSDCI 3-A.1 GB
3. RATING CONDITIONS
Standard conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and
EN 14511.
Cooling:
Indoor: 27
o
C DB 19
o
C WB
Outdoor: 35
o
C DB
Heating:
Indoor: 20
o
C DB
Outdoor: 7
o
C DB 6
o
C WB
3.1 Operating Limits
Indoor Outdoor
Cooling
Upper limit 32
o
C DB 23
o
C WB 46
o
C DB
Lower limit 21
o
C DB 15
o
C WB -10
o
C DB
Heating
Upper limit 27
o
C DB 24
o
C DB 18
o
C WB
Lower limit 10
o
C DB -15
o
C DB -16
o
C WB
Voltage
1PH
198 - 264 VAC
3PH
323 - 440 VAC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Airwell DLSE Series and is the answer not in the manual?

Airwell DLSE Series Specifications

General IconGeneral
BrandAirwell
ModelDLSE Series
CategoryInverter
LanguageEnglish

Related product manuals