11-9
CONTROL SYSTEM
SM PNXDCI 1-A.1 GB
Water Level
ANY
0
BLINK
NLOAD
OPER LED
LEVEL1
LEVEL 3
LEVEL4
NORMAL
ON
Pump
OFF
11.8.2 1 Level Logic (used in all models except for floor/ceiling
models)
P2 P3 Level
Don`t
care
1 Normal
Don`t
care
0 Overflow
ANY
0
ON
NLOAD
PUMP
OFF
ON
OPER
LED
OFF
Overflow
Water Level
Normal
BLINK
NLOAD is
forced to 0
8min 8min
Overflow when
unit is ON
Overflow when
unit is OFF
8min
11.9 Indoor Unit Dry Contact
Indoor unit Dry contact has two alternative functions that are selected by J8.
Function Contact = Open Contact = Short
J8 Presence Detector Connection No Limit Forced to STBY=Open
J8 Power Shedding Function No Limit Limit NLOAD=Open