Installation and Operations Guide
|
MS/TP Microset II
30
LTBT-MSTPMS2IOG Rev. 02 © Honeywell
setpoint.
Hotel modes
Hotel modes have a feature set typically used in the hospitality industry.
M6—Hotel, No Fan, Rented
Set BV-64 and BV-81 ON and BV-80 OFF. Operation depends on whether the
unit is ON or OFF.
This mode’s counterpart is M7, which is activated by setting BV-64 OFF.
Operation when ON
The LCD displays the occupant selected space temperature setpoint (AV-90).
The unit controls to occupied heating and cooling setpoints.
The setpoint remains
displayed until a right
button is pressed or the
after-hours timer expires
Adjust setpoint
Return to after-hours
adjustment mode (either
button)