Installation and Operations Guide
|
Field service mode
© Honeywell LTBT-MSTPMS2IOG Rev. 02
35
Field service mode
Field service mode enables technicians to query and command key operating
variables in the MS/TP Microset II. A technician presses a particular button
sequence at the MS/TP Microset II to enter field service mode. In field service
mode a technician uses the left buttons to scroll through data codes and the right
buttons to change the value associated with a code.
The lower left of the LCD shows the two-digit data code and the main area
displays the data value. A pre-defined list of data codes is available (see Table 6
on page 36).
Note Fixed codes appear with a period after them, which enables a technician
to distinguish them quickly from custom codes.
The data range in field service mode is –3276 to 3276. When a data value is less
than -999.9, the decimal point is automatically dropped.
Set BV-68 ON (field service lockout) to deny access to field service mode.
Field service mode ends automatically if there is no button activity for 40
minutes.
To start field service mode
1. Press and release the left UP button and right UP buttons simultaneously.
2. Repeat step 1.
3. Press the right
UP button.
4. Use the left
UP/DOWN buttons to set the lower right display item to the
number 7.
5. Press the right
UP button.