M9—Hotel, Fan, Vacant
Set BV-64 OFF and BV-80 and BV-81 ON. The display is blank. The unit
controls to unoccupied heating and cooling setpoints.
This mode’s counterpart is M8, which is activated by setting BV-64 ON.
Vacant mode offers a temporary housekeeping override function. Housekeeping
can press the right
UP button to activate the override, which sets the timer to the
override limit (AV-97).
Housekeeping override operation
The LCD displays the override time remaining. The unit controls to occupied
setpoints while the override timer (AV-98) is non-zero.
Housekeeping can press the right
DOWN button to cancel the override. The timer
can’t restart until it has timed down or been canceled. The setpoint is not
adjustable.
Activate housekeeping
override
Cancel housekeeping
override
Housekeeping override
time remaining in hh:mm