2–4 Installation
Publication 1203–5.1 –– July, 1997
Figure 2.2
SW3 Flowchart continued
Will Datalink Group B be used?
Step 5. Datalink B Transfer
YES
NO
1. Write “Datalink B“ in the output and input image
of the next two available words
2. Set SW3-5 to on
Will Datalink Group C be used?
Step 6. Datalink C Transfer
YES
NO
1. Write “Datalink C” in the output and input image
of the next two available words
2. Set SW3-6 to on
Will Datalink Group D be used?
Step 7. Datalink D Transfer
YES
NO
1. Write “Datalink D” in the output and input image
of the next two available words
2. Set SW3-7 to on
Step 9. Calculate minimum rack size
Refer to Table 2.A on page page 2–3.
1. Record the minimum rack size in Table 2.A on page 2–3.
2. Use the minimum rack size to set Dip switches SW2-1 and SW2-2.
Will the last Datalink be one word
(truncate last Datalink) ?
Step 8. Truncate Last Datalink
YES
NO
1. Cross out the last word of the last Datalink group
used in the output and input image table
2. Set SW3-8 to on
2. Move to step 6
1. Set SW3-5 to off
2. Move to step 7
1. Set SW3-6 to off
2. Move to step 8
1. Set SW3-7 to off
2. Move to step 9
1. Set SW3-8 to off
Will Datalink Group A be used?
4. Datalink A Transfer
YES
NO
1. Write “Datalink A” in the output and input image
of the next two available words
2. Set SW3-4 to on
Step
2. Move to step 5
1. Set SW3-4 to off

Other manuals for Allen-Bradley 1203-GD1