Publication 1734-UM014A-EN-P - November 2010
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 57
The New Module properties dialog opens.
9. Verify that the requested packet interval (RPI) is appropriate for your
system. You use this value for the rack-optimized connection to the I/O
modules.
10. Click OK. The name of the adapter appears in the I/O tree.
To avoid overloading the adapter, we recommend that you set RPI no
less than 10 ms for rack connections and 50 ms for direct connections.