Module Installation
This module mounts on a 1794 terminal base unit.
1. Rotate keyswitch (1) on terminal base unit (2) clockwise to position 2
as required for this type of module.
2. Make certain the flexbus connector (3) is pushed all the way to the left
to connect with the neighboring terminal base/adapter. You cannot
install the module unless the connector is fully extended.
3. Make sure that the pins on the bottom of the module are straight so
they will align properly with the connector in the terminal base unit.
4. Position the module (4) with its alignment bar (5) aligned with the
groove (6) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base unit.
The module is seated when the latching mechanism (7) is locked into
the module.
!
ATTENTION: To use this module in a complementary
I/O system, refer to your Remote I/O Adapter module
documentation.
Installation Instructions
Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1794-OB16 and is the answer not in the manual?

Allen-Bradley 1794-OB16 Specifications

General IconGeneral
ManufacturerAllen-Bradley
Module TypeDigital Output
Output TypeSourcing
Number of Outputs16
Output Voltage24V DC
Output Current0.5 A per point, 8 A per module
Series1794
Communication InterfaceBackplane
Product TypeOutput Module
Isolation Voltage500V AC
Operating Temperature0-60°C
Module LocationFlex I/O
Operating Voltage20.4 to 26.4V DC
Backplane Current100mA at 5V DC
Current Draw100mA at 5V DC

Summary

Installation Instructions

Module Installation Guide

Step-by-step guide for mounting the 24V dc FLEX I/O module onto a terminal base unit.

Terminal Base Unit Wiring

Wiring Procedure

Connect output wiring, common, +24V dc power, and dc return to the terminal base unit.

Output Configuration and Data Mapping

Output to Terminal Assignments

Table detailing output numbers, their corresponding terminals, and common connections.

Module Technical Specifications

General Technical Data

Key technical parameters including output count, voltage range, current rating, and signal delay.

CSA Hazardous Location Safety Precautions

Explosion Hazard Prevention

Warnings regarding component substitution, power handling, and connector security in hazardous areas.